Abstract:
为了有效回收空调机房排风热量,提出气泵和压缩机热回收系统,设计出样机并应用于北京某实验基地的空调机房.当新风进口温度从3 ℃升至15 ℃时,通过实际测试获得了气泵系统和压缩机系统的制热量、功率、温度效率、新风出口温度、性能系数(COP)及节能率.结果表明:当新风进口温度低于7 ℃时,气泵系统性能较好;当新风进口温度高于等于7 ℃时,压缩机系统性能较好;与采用电锅炉相比,气泵系统和压缩机系统的节能率分别为38.85%、35.25%.