In space heating, air source heat pumps (ASHPs) always encounter mal-defrosting incidents, resulting in significant energy waste. To improve the defrosting accuracy of ASHP, this paper proposes a novel Time-CurrentTemperature difference (T-I-T) defrosting control method based on the characteristic parameter of outdoor fan operation (current). Through theoretical analysis and experimental tests, the influence of frosting on the characteristic parameters of outdoor fan operation was revealed. Then, based on the optimal defrosting control point theory, a method for selecting the defrosting current threshold close to the actual ASHP was proposed. Ultimately, a novel Time-Current-Temperature Difference (T-I-T) defrosting control method was developed, using the current increment to control the defrosting operation. The results showed that, the defrosting current thresholds decreased as the severity of frosting decreases, from 1.52 to 0.78 A. The T-I-T defrosting control method enables the ASHP unit to operate stably and efficiently in space heating. The defrosting frequency decreased from 0.93 to 0.56 times per hour, a reduction of 39.80 %; the average duration of the frosting/ defrosting cycle increases from 64.30 to 106.90 min (an increase of 66.25 %), and the average COP of the ASHP unit increases by 10.60 % compared to the T-T defrosting control method.

Keyword:

Time-Current-Temperature Difference Defrosting current threshold Air source heat pump Outdoor fan operating parameters defrosting control method

Author Community:

  • [ 1 ] [Tang, Rui]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China
  • [ 2 ] [Wei, Wenzhe]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China
  • [ 3 ] [Zhao, Jihan]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China
  • [ 4 ] [Wang, Wei]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China
  • [ 5 ] [Sun, Yuying]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China
  • [ 6 ] [Sun, Ping]Qingdao Prod Qual Testing Res Inst, Qingdao 266101, Peoples R China
  • [ 7 ] [Wang, Wei]Beijing Polytech, Coll Mechatron Engn, Beijing 100176, Peoples R China
  • [ 8 ] [Deng, Shiming]Qatar Univ, Dept Mech & Ind Engn, POB 2713, Doha, Qatar

Reprint Author's Address:

  • 王伟

    [Wei, Wenzhe]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China;;[Wang, Wei]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China;;[Wang, Wei]Beijing Polytech, Coll Mechatron Engn, Beijing 100176, Peoples R China

Show more details

Related Keywords:

Related Article:

Source :

APPLIED THERMAL ENGINEERING

ISSN: 1359-4311

Year: 2024

Volume: 259

6 . 4 0 0

JCR@2022

Cited Count:

WoS CC Cited Count:

SCOPUS Cited Count:

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 0

Affiliated Colleges:

Online/Total:525/5427930
Address:BJUT Library(100 Pingleyuan,Chaoyang District,Beijing 100124, China Post Code:100124) Contact Us:010-67392185
Copyright:BJUT Library Technical Support:Beijing Aegean Software Co., Ltd.