收录:
摘要:
To improve the defrosting accuracy of air source heat pumps (ASHPs), this paper proposes a novel defrosting control method by applying tube encircled photoelectric sensors (TEPSs). A field test was conducted for two heating seasons in Beijing, China, to verify the feasibility and practicality of the novel TEPS method. The test results revealed that irrespective of the environmental conditions, the TEPS method can initiate defrosting in similar situations: most of the heat exchanger surface had been covered by frost; the compressor suction temperature decreased by similar to 9 degrees C; the compressor discharge temperature increased by similar to 16 degrees C; and the heating capacity decreased by similar to 30%. Furthermore, the TEPS method was verified to make more accurate and more reasonable defrosting decisions than the traditional T-T method under both frosting and non-frosting conditions. The results indicate that the TEPS method is a competitive defrosting control method that can be used for ASHPs. (C) 2015 Elsevier Ltd and IIR. All rights reserved.
关键词:
通讯作者信息:
电子邮件地址:
来源 :
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
ISSN: 0140-7007
年份: 2016
卷: 66
页码: 133-144
3 . 9 0 0
JCR@2022
ESI学科: ENGINEERING;
ESI高被引阀值:166
中科院分区:2