To improve the defrosting accuracy and the energy efficiency of the air-source heat pump (ASHP) under frosting and defrosting conditions, a novel Temperature-Humidity-Time (T-H-T) defrosting control method, based on a frosting map for the ASHP unit, is proposed in this paper. A field test was conducted for two heating seasons, to verify the feasibility and applicability of the T-H-T method. The advantages of the T-H-T method, compared to the conventional Temperature-Time (T-T) defrosting control method, are presented. In total, eight cases are shown in this paper. Cases 1 to 4 were chosen to reveal the T-H-T performance under different frosting conditions. It was found that no matter what kind of frosting conditions, defrosting was always initiated in a similar situation: similar to 90% of the outdoor coil surface was covered by frost; the temperature difference between the compressor suction and discharge increased by similar to 20%; and the heating capacity decreased by similar to 30%. These results indicate that the T-H-T method can make an accurate decision under different frosting conditions. Cases 5a, 5b and Cases 6a, 6b were two groups of cases to compare the advantages of the T-H-T method against the conventional T-T method. Cases 5a and 5b were chosen for the non-frosting condition. It was found that the T-T method initiated the defrosting operation 31 times within 24 h. However, none of the defrosting operations was conducted for the T-H-T method. Cases 6a and 6b were chosen to compare these two methods under consecutive and variable frosting conditions. For the T-T method, 63% of the defrosting processes were found to be executed under conditions where defrosting was not necessary. However, for the T-H-T method, all the defrosting controls were found to be accurate and reasonable. These results indicated that the novel T-H-T method is suitable for the defrosting control of the ASHP, and has a more competitive performance than the conventional T-T method. (C) 2015 Elsevier Ltd and IIR. All rights reserved.

关键词:

Air-source heat pump Field test Frosting rate Defrosting control method Defrosting interval Frosting map

作者机构:

  • [ 1 ] [Zhu, Jiahe]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 2 ] [Sun, Yuying]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 3 ] [Wang, Wei]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 4 ] [Ge, Yijing]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 5 ] [Li, Lintao]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 6 ] [Liu, Jingdong]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China

通讯作者信息:

  • 王伟

    [Wang, Wei]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, 100 Pingleyuan Rd, Beijing 100124, Peoples R China

电子邮件地址:

查看成果更多字段

相关关键词:

来源 :

INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID

ISSN: 0140-7007

年份: 2015

卷: 54

页码: 45-54

3 . 9 0 0

JCR@2022

ESI学科: ENGINEERING;

ESI高被引阀值:174

JCR分区:1

中科院分区:2

被引次数:

WoS核心集被引频次: 96