摘要:

To quantify the performance drop of the air source heat pump (ASHP) system under a special kind of mal-defrost phenomenon appearing in moderate climate conditions, a field test was conducted for 8 days at the initial stage of a heating season in Beijing, China. The mal-defrost was found with the more than 60% frosted area of the outdoor heat exchanger after the system running 5 days. During this frosting period, the system COP was significantly degraded, only 2.3 under an environment temperature of 7.9 degrees C. Comparing the test data before and after frosting, it was found that the mal-defrost decreased the COP up to 40.4% and the heating capacity to 43.4%. Such low energy efficiency continued quite a long time until the defrost control was started up manually by the authors. After defrosting, the COP reclaimed to the normal level of 5.0. The origins of this special mal-defrost phenomenon were discussed. And some suggestions were proposed to modify the current defrosting control strategy, which were helpful to avoid the mal-defrost problem in the current ASHP system and therefore improve the system performances. (C) 2012 Elsevier Ltd. All rights reserved.

关键词:

Air source heat pump COP Heating capacity Mal-defrost

作者机构:

  • [ 1 ] [Wang, W.]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 2 ] [Feng, Y. C.]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 3 ] [Zhu, J. H.]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 4 ] [Li, L. T.]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 5 ] [Guo, Q. C.]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China
  • [ 6 ] [Lu, W. P.]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, Beijing 100124, Peoples R China

通讯作者信息:

  • 王伟

    [Wang, W.]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, 100 Pingleyuan, Beijing 100124, Peoples R China

电子邮件地址:

查看成果更多字段

相关关键词:

来源 :

APPLIED ENERGY

ISSN: 0306-2619

年份: 2013

卷: 112

页码: 1138-1145

1 1 . 2 0 0

JCR@2022

ESI学科: ENGINEERING;

ESI高被引阀值:131

JCR分区:1

中科院分区:1

被引次数:

WoS核心集被引频次: 77

SCOPUS被引频次: 88

ESI高被引论文在榜: 0 展开所有

万方被引频次:

中文被引频次:

近30日浏览量: 2

在线人数/总访问数:589/2909726
地址:北京工业大学图书馆(北京市朝阳区平乐园100号 邮编:100124) 联系我们:010-67392185
版权所有:北京工业大学图书馆 站点建设与维护:北京爱琴海乐之技术有限公司