收录:
摘要:
In engineering practice, refrigerant contains lubricating oil form compressor in the refrigerating system. In this study, the impact of different oil contents on evaporation of falling film on horizontal enhanced tube was discussed. Experiments were conducted for R134a at the saturation temperature of 6 on enhanced copper tube, with oil contents being 0.5%, 1.2% and 5.1%, respectively, and heat fluxes ranging from 30 kW/m2 to 65 kW/m2, sprinkle densities being 0.13, 0.17, and 0.21, kg/(s·m). The experimental results show that heat transfer coefficient of the outside horizontal enhanced tube increases with both oil contents growing from 0.5% to 5.1% and increasing sprinkle densities. However, with the augments of oil contents, the increases of heat transfer coefficient are nearly insensitive to the increasing sprinkle densities. In certain range of content, lubricating oil can improve heat transfer coefficient of R134a falling film evaporation. ©, 2015, Tianjin University. All right reserved.
关键词:
通讯作者信息:
电子邮件地址:
来源 :
Journal of Tianjin University Science and Technology
ISSN: 0493-2137
年份: 2015
期: 7
卷: 48
页码: 591-595