• 综合
  • 标题
  • 关键词
  • 摘要
  • 学者
  • 期刊-刊名
  • 期刊-ISSN
  • 会议名称
搜索

作者:

Zhao, Yao-Hua (Zhao, Yao-Hua.) (学者:赵耀华) | Yu, Wen-Jing (Yu, Wen-Jing.) | Diao, Yan-Hua (Diao, Yan-Hua.) | Zhang, Ji (Zhang, Ji.) | Hao, Li-Min (Hao, Li-Min.)

收录:

EI Scopus PKU CSCD

摘要:

A plate heat pipe heat exchanger for room ventilation is designed. Its performance affected by vacuum is experimentally investigated. Experiments were carried out under the simulated summer condition. The air volume rates were changed at 60, 90, 120, and 150 m3/h. The fresh air temperature varied from 27 to 40°C, whereas the return air temperature was kept at about 24°C. Results show that the conservation effect of the heat pipe heat exchanger is prominent and the maximum effectiveness is about 60%. The change for effectiveness is slightly different from variation of vacuum.

关键词:

Atmospheric temperature Heat convection Heat exchangers Heat pipes Vacuum Ventilation Waste heat Waste heat utilization

作者机构:

  • [ 1 ] [Zhao, Yao-Hua]College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100124, China
  • [ 2 ] [Yu, Wen-Jing]College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100124, China
  • [ 3 ] [Diao, Yan-Hua]College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100124, China
  • [ 4 ] [Zhang, Ji]College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100124, China
  • [ 5 ] [Hao, Li-Min]College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100124, China

通讯作者信息:

电子邮件地址:

查看成果更多字段

相关关键词:

相关文章:

来源 :

Journal of Beijing University of Technology

ISSN: 0254-0037

年份: 2012

期: 4

卷: 38

页码: 497-501

被引次数:

WoS核心集被引频次: 0

SCOPUS被引频次:

ESI高被引论文在榜: 0 展开所有

万方被引频次:

中文被引频次:

近30日浏览量: 1

在线人数/总访问数:189/3603435
地址:北京工业大学图书馆(北京市朝阳区平乐园100号 邮编:100124) 联系我们:010-67392185
版权所有:北京工业大学图书馆 站点建设与维护:北京爱琴海乐之技术有限公司