A plate heat pipe heat exchanger for room ventilation was designed. The advantages of the heat pipe heat exchanger are small and high compactness. In this paper, the effect of the working fluid (R113, R141b and their mixture) was investigated experimentally for the performance of the heat pipe heat exchanger. The overall experiments were carried out under the simulated summer condition, the vacuum of the heat pipe heat exchanger was set at 1 × 10-3 Pa, and the filling ratio (the ratio of the working fluid volume in the heat pipe heat exchanger to the volume of the heat pipe heat exchanger) was 1/3. The experimental results show that the heat pipe heat exchanger could gain a high efficiency of heat recovery. The effectiveness of heat pipe heat exchanger with R141b as working fluid is superior to other working fluid over the whole air volume range, and the maximum effectiveness could be reached 58.2%.