收录:
摘要:
The paper studied 28 kHz ultrasonic anti-fouling performance by cooling water treatment under the different temperature and hardness through fouling resistance dynamic monitoring method. The experimental results showed that ultrasonic water treatment has obvious antifouling effect. The ultrasonic anti-fouling device has the better anti-fouling effect and can greatly increase the heat transfer coefficients at low water hardness. The ultrasonic anti-fouling device can also reduce Ca2+ separate out from hard water. © 2015, Science Press. All right reserved.
关键词:
通讯作者信息:
电子邮件地址: