The relativity between nitrate concentration at the end of anoxic zone and oxidation-reduction potential (ORP) was studied by using starch wastewater. Results show that the relativity between them is very good, and ORP can be worked as nitrate recirculation flow and external carbon dose on-line fuzzy control parameters respectively. The ORP fuzzy controller was designed. The controlling nitrate recirculation flow and external carbon dose, keeping ORP in (-86±2) mV and (-90±2) mV, respectively, can realize A/O process as the optimal control for nitrogen removal.